communication ports
- Sub-LAN port Baud Rate: 9,600
- Protocol: Proprietary
- Transport: RS485 multi-drop bus asynchronous, polling (open or closed loop)
network wiring requirements
- Length
5,000 ft, 1,500m max @ 22AWG
4,000 ft, 1,200m max @ 24AWG
- Cable Size
22 or 24AWG, 0.35 or 0.25mm2
- Impedance: 85 to 150 Ohm
- Capacitance
<30pF/ft between
conductors and
<55pF/ft conductor to shield
- Cable Ttype
Belden 9184 2pr 22AWG
Belden 9841 1pr 24AWG
or equivalent twisted shielded pair
reader wiring requirements
- I\DISC
2 twisted pair shielded 200ft,
60m max
Belden #9184 or 9855
- Wiegand
8 conductor shielded
500ft, 150m max
Belden #9536 or 9537
- Wiegand –Prox
8 conductor shielded, 150-350ft,
50-100m max (see reader guide)
Belden #9536 or 9537
- ABA 115 & 85
8 conductor shielded 200ft, 60m max
Belden #9305 or 8725
hardware details
- Processor: Renesas H8S Series
- Static RAM: 2Mb
- Flash Memory: 1/2Mb
- RAM Battery backup
2 x Ni-Mh rechargeable, replaceable,
30 days backup
environment
- Operating Temperature
32°F to 122°F, 0°C to 50°C without
battery-backup 50°F to 100°F,
10°C to 40°C with lead-acid battery
- Operating Humidity
10-80% RH, non-condensing
battery backup option
- Type
Sealed Rechargeable Lead-Acid,
Maintenance Free,
- Capacity
4AH, 12Vdc 4 hours operation
min. (excluding lock power, which
must be provided separately)
- Charge Current
2A max (short circuit), 0.8A typical
scu power requirements
- Power Input
SCU12xx - 24VAC 1.2A max
SCU12xxE1 or E2 –115Vac 75 VA max
SCU12xxE3 –230Vac 75VA max
(50/60 Hz +-15%)
- Power Failure Notification
Standard, internal monitoring of AC
power input
|